Standard:
ISO/IEC 11801, IEC 61156-5
EN 50173, EN 50288, TIA/EIA-568
CONSTRUCTION:
Conductor: copper (bare, solid), diameter
0,51 mm, AWG24, cl. 1
Insulation: solid polyethylene (PE), outer diameter, approx. 1,1 mm
Twisting elements: two cores twisted in pairs
Cable core: 4 stranded pairs
Common screen: Al laminated plastic foil + tinned Cu drain wire, diameter 0,48 mm AWG26
Outer sheath: PVC, or halogen-free (LSZH, LSOH, FRNC), external diameter, approx.: 5,9-6,6 mm
Sheath color: dark grey (PVC) or orange (LSZH)
Behavior in fire:
Self-extinguishing cable acc. to IEC 60332-1/
EN 60332-1/VDE 0482-332-1
LSZH (FRNC-C) version, additionally:
halogen-free acc. to IEC 60754-1;
non-corrosive combustion gases acc. to
IEC 60754-2;
minimal smoke release acc. to IEC 61034-2
resistant to flame propagation acc. to
IEC 60332-3 (LSZH-FR, LSFROH, FRNC-C)
APPLICATION:
Cable applied in structured cabling system of class D for high-speed data and voice transmission, at primary, secondary (vertical) and tertiary (horizontal) level.
Standardized for application up to 155 MHz
Can be laid in cable canals.
The permissible temperature range:
– during installation: 0°C up to +50°C
– operating temperature: -20°C up to +60°C
Minimal inner bending radius:
– fixed: 4D (25 mm)
– at installation: 8D (50 mm)
(D – external cable diameter)
Maximal tensile strength: 80 N