Standard: SRPS N.C3.410
DIN VDE 0282-3, HD 22.3 S3, IEC 60245-3
Nominal voltage U0/U: 300/500 V
Test voltage: 2,0 kV
CONSTRUCTION
Conductor: copper conductor class 5, prema
IEC 60228, HD 383, DIN VDE 0295.
Insulation: rubber compound based on silicone rubber
Flame retardant: according to IEC 60332-1
Halogen free: acc. to IEC 60754-1
Corrosiveness of combustion gases: not corrosive acc. to IEC 60754-2
APPLICATION
Silicone installation wires are intended for
electric power installation at place where
temperature is higher than temperature
environment or below 0°C.
Permissible conductor temperature:
– max operating temperature +180°C
– in short circuit (max 5 s), max. +250°C
Permissible environment temperature:
– mobile from -50°C to +180°C
– fixed laying from -60°C to +200°C
BENDING RADIUS (min.):
Smallest bending radius: 4D
(D – cable diameter).
Maximal tensile strength of insulation:
– under normal conditions: 5 N/mm2
– after ageing (24h/200°C): 4 N/mm2
Specific electrical resistance of insulation:
>200 MΩxkm
POSSIBLE INSULATION COLOURS:
Silicone rubber insulated fine wired – Si/F
Standard: SRPS N.C3.410
DIN VDE 0282-3, HD 22.3 S3, IEC 60245-3
Nominal voltage U0/U: 300/500 V
Test voltage: 2,0 kV
CONSTRUCTION
Conductor: copper conductor class 5, prema
IEC 60228, HD 383, DIN VDE 0295.
Insulation: rubber compound based on silicone rubber
Flame retardant: according to IEC 60332-1
Halogen free: acc. to IEC 60754-1
Category: Silicone insulated conductors and cables