Standard:
VDE 0815/85 + A1/88
CONSTRUCTION:
Conductor: soft annealed copper wire diameter of
0,6 mm and 0,8 mm, class 1
(EN 60228)
Insulation: PVC compound type YI1, acc. to
VDE 0207/3 (EN 50290-2-21)
Twisting elements: pairs
(except construction of two pairs being twisted to star quad)
Colour code: according to VDE 0815
(for concentrically stranding)
Cable core: concentrically stranded
Core wrapping: termoplastic tapes (polyester)
Screen: one side laminated aluminium foil (Al polyester) with a copper drain wire longitudinally applied under it.
Outer sheath: PVC sheath type YM1, acc. to
VDE 0207/3 (EN 50290-2-22).
Sheath colour gray RAL 7032.
Flame retardant:
VDE 0482-332-1-2/IEC 60332-1
APPLICATION:
For connection of telecommunication units inside of buildings in dry and wet rooms, also outdoors if the cable is protected against direct sun irradiation.
Telephone installation cables are not allowed for purposes of high current and power installation.
The permissible temperature range:
– during installation: from -5°C to +50°C
– during operation: from -30°C to +70°C
Min. permissible bending radius: according to DIN VDE 0891 part 5
– during operation max. 7,5D
– single bending without stress max. 2,5D
(D – outer diameter of cable)