Standard:
VDE 0815/85 + A1/88
CONSTRUCTION:
Conductor: soft annealed copper wire diameter of
0,8 mm, class 1 (EN 60228)
Insulation: PVC compound type YI1, acc. to VDE 0207/3 (EN 50290-2-21)
Twisting elements: pairs
(except construction of two pairs being twisted to star quad)
Colour code: according to VDE 0815
(for concentrically stranding)
Cable core: concentrically stranded
Core wrapping: termoplastic tape (polyester)
Screen: one side laminated aluminium foil (Al polyester) with a copper drain wire longitudinally applied under it.
Outer sheath: PVC sheath type YM1, acc. to
VDE 0207/5 (EN 50290-2-22).
Sheath colour red, RAL 3000.
Flame retardant:
VDE 0482-332-1-2/IEC 60332-1
APPLICATION:
For the connection of telecommunication units inside buildings in and under plaster in dry and wet rooms. Also suitable for installation outdoors if the cable is protected from sunlight. By the special sheath imprint: Brandmelde – this cable is particularly designed for the use in fire signalisation systems.
Not approved for power and underground installation.
The permissible temperature range:
– during installation: from -5°C to +50°C
– during operation: from -30°C to + 70°C
Min. permissible bending radius:
– during operation max. 7,5D
– single bending without tension max. 2,5D
(D – outer diameter of cable)