Standard: HD 22.9
DIN VDE 0282 part 9
Nominal voltage U0/U: 450/750 V
Test voltage: 2,5 kV
CONSTRUCTION
Conductor: solid annealed copper conductor, according to DIN VDE 0295, IEC 60228, for type:
H07Z-U solid, class 1
H07Z-R multi-core, class 2
H07Z-K multi-core, class 5
Insulation: slow-burning material – based on
the polyolefin or the suitable synthetic polymer
(EI5, DIN VDE 0282-1)
Flame retardant: IEC 60332-1
Halogen-free: IEC 60754-1
Non-corrosive combustion gases: IEC 60754-2
Low smoke density: IEC 61034-2
APPLICATION
Halogen-free conductors used for installations in dry environment for wiring of lighting fixtures, tools and other devices in facilities where human lives or valuable property need to be protected against damages caused by fire.
Laid on or under plaster, same as in closed installation canals.
Permissible conductor temperature:
– max operating temperature +90°C,
– in short circuit (max 5 s), max +250°C
Permissible environment temperature:
at laying and handling, min +5°C
at storage, max +40C
BENDING RADIUS (min.):
– single core cables 4D; (D – cable diameter).
POSSIBLE INSULATION COLOURS: