Standard: DIN VDE 0266
Nominal voltage U0/U: 0,6/1 kV
Test voltage: 4 kV
CONSTRUCTION
Conductor: solid annealed copper conductor, class 1 or multi wire class 2, according to
DIN VDE 0295, IEC 60228
Wrapping: Fiber glass textile tape (mica tape)
Insulation: cross-linked halogen-free polymer, HXI1 acc. to DIN VDE 0266
Core: concentrically stranded cores, colour marked acc. to HD 308 S2/VDE 0293-308, with or without protective yellow-green conductor
Filler: extruded halogen free layer over stranded cores.
Concentric conductor: copper wire with
counter spiral made from copper tape
Sheath: halogen free corsslinked compound
base on polyolefin (HXM1, prema DIN VDE 0266).
Sheath colour: orange
Flame retardant: IEC 60332-1
No flame propagation: IEC 60332-3 cat. C
Insulation integrity: IEC 60331
Halogen-free: IEC 60754-1
Non-corrosive combustion gases: IEC 60754-2
Low smoke density: IEC 61034-2
Function integrity: DIN VDE 4102/12 of electrical cable system for a period of 30-90 min.
APPLICATION
Cables are intended for installation in buildings
with increased requirements for safety of people
and property, in buildings where the rescue of
people and animals is difficult (high buildings all
types in which resides a number of people and
animals), public, business and other objects for
which if very important not to spread fire fast
and endangering people with smoke. It is allowed to be put in the open air. Cables can supply power in the fire, min. 180 minute (FE-180).
Permissible conductor temperature:
– max operating temperature +90°C
– in short circuit (max 5 s), max +250°C
Permissible environment temperature:
– at laying and handling, min +5C to +50C
BENDING RADIUS (min.):
– single core cables 15D; (D – cable diameter)
– multi-wires cable 12D
Halogen free cable with improved characteristics in fire – NHXCHX FE-180 E30/E90
Standard: DIN VDE 0266
Nominal voltage U0/U: 0,6/1 kV
Test voltage: 4 kV
CONSTRUCTION
Conductor: solid annealed copper conductor, class 1 or multi wire class 2, according to
DIN VDE 0295, IEC 60228
Wrapping: Fiber glass textile tape (mica tape)
Insulation: cross-linked halogen-free polymer, HXI1 acc. to DIN VDE 0266
Category: Halogen free conductors and cables
Description
Tel: +381 11 328 25 10
Tel/Fax: +381 11 328 25 41
E-mail: coptech@sbb.rs | info@coptech.rs
Main address: Peke Pavlovića 16, 11000 Beograd
Office address: Kneza Mihailova 21/10, 11000 Beograd
Business unit address in Jagodina: Kneza Lazara 187, 35000 Jagodina
MB:20311819 | PIB:105087097
Accounts info:
160-278653-63 Banca Intesa ad
205-159358-30 Komercijalna banka